STANDARD DUCT RM_BTP

Eurovent

SCOP MAX

4.81

Capacity

5kW – 16kW

Operation

-27°C/+52°C (SDI) -15°C/+46°C (DI)

Warranty

5 years

SCOP MAX

4.81

Capacity

5kW – 16kW

Operation

-27°C/+52°C (SDI) -15°C/+46°C (DI)

Warranty

5 years

Whatever the shape of the room, this flexible unit ensures a uniform temperature and air distribution for optimal end user comfort.

Adaptability

Adaptability

  • Up to 120Pa available pressure, thanks to DC fan motor
  • Flexible design allows the inlet air to be configured between the standard rear inlet design or as an alternative, from the underside of the unit.
  • There is also a provision for a fresh air intake supply via a pre-punched knockout hole
    aCompact and thin chassis, measuring just 275mm in height
Easy installation

Easy installation

  • Built-in high-lift drain pump
  • PC board panel easily accessible from the side of the unit
  • Optional air discharge spigot
PERFORMANCE DATA WITH SUPER DIGITAL INVERTER
OUTDOOR UNIT
RAV-GP561ATP-E
RAV-GP801AT-E
RAV-GP1101AT-E
RAV-GP1101AT8-E
RAV-GP1401AT-E
RAV-GP1401AT8-E
RAV-GP1601AT8-E
-
-
INDOOR UNIT
RAV-RM561BTP-E
RAV-RM801BTP-E
RAV-RM1101BTP-E
RAV-RM1101BTP-E
RAV-RM1401BTP-E
RAV-RM1401BTP-E
RAV-RM1601BTP-E
-
-
Cooling capacity kW
5,0
7,1
10,0
10,0
12,5
12,5
14,0
-
-
Cooling range (min. - max.) kW
1,2-5,6
1,9 - 8,0
3,1 - 12,0
2,6 - 12,0
3,1 - 14,0
2,6 - 14,0
2,6 - 16,0
-
-
EER
3,29
4,36
4,17
3,88
3,50
3,28
3,12
-
-
SEER
5,60
7,50
6,60
5,70
6,06
5,48
5,36
-
-
Energy efficiency class
A+
A++
A++
A+
TBD
TBD
TBD
-
-
Heating capacity kW
5,6
8,0
11,2
11,2
14,0
14,0
16,0
-
-
Heating range (min. - max.) kW
0,9-7,4
1,3 - 11,3
2,6 - 13,0
2,40 - 15,6
2,6 - 16,5
2,40 - 18,0
2,4 - 19,0
-
-
COP W/W
3,48
4,32
4,10
4,06
3,86
3,83
3,50
-
-
SCOP (Average)
4,24
4,81
4,24
4,14
4,24
3,95
3,93
-
-
Energy efficiency class (Average) H
A+
A++
A+
A+
TBD
TBD
TBD
-
-
PERFORMANCE DATA WITH DIGITAL INVERTER
OUTDOOR UNIT
RAV-GM561ATP-E
RAV-GM801ATP-E
RAV-GM901ATP-E
RAV-GM1101ATP-E
RAV-GM1101AT8P-E
RAV-GM1401ATP-E
RAV-GM1401AT8P-E
RAV-GM1601ATP-E
RAV-GM1601AT8P-E
INDOOR UNIT
RAV-RM561BTP-E
RAV-RM801BTP-E
RAV-GM901BTP-E
RAV-RM1101BTP-E
RAV-RM1101BTP-E
RAV-RM1401BTP-E
RAV-RM1401BTP-E
RAV-RM1601BTP-E
RAV-RM1601BTP-E
Cooling capacity kW
5,0
6.7
8.0
9.5
9,5
12,1
12,1
14,0
14,0
Cooling range (min. - max.) kW
1,5 - 5,6
1,5 - 8,0
1,9 - 8,8
3,0 - 11,2
3,0 - 11,2
3,0 - 13,2
3,0 - 13,2
3,0 - 16,0
3,0 - 16,0
EER
2,73
2,82
3,00
3,18
3,18
2,74
2,74
2,73
2,73
SEER
5,28
5,20
6,10
5,28
5,28
5,36
5,36
5,3
5,3
Energy efficiency class
A
A
A++
A
A
TBD
TBD
TBD
TBD
Seasonal electricity consumption kWh/a C
332
451
459
629
629
TBD
TBD
TBD
TBD
Heating capacity kW
5,3
7,7
9,0
11,2
11,2
13,0
13,0
16,0
16,0
Heating range (min. - max.) kW
1,5 - 6,3
1,5 - 9,0
1,6 - 9,9
3,0 - 13,0
3,0 - 13,0
3,0 - 16,0
3,0 - 16,0
3,0 - 18,0
3,0 - 18,0
COP W/W
3,27
3,32
3,40
3,75
3,75
3,61
3,61
3,41
3,41
SCOP (Average)
4,08
4,13
4,60
4,19
4,19
4,19
4,19
3,9
3,9
Energy efficiency class (Average) H
A+
A+
A++
A+
A+
TBD
TBD
TBD
TBD
PHYSICAL DATA INDOOR
INDOOR UNITS
RAV-RM561BTP-E
RAV-RM801BTP-E
RAV-GM901BTP-E
RAV-RM1101BTP-E
RAV-RM1401BTP-E
RAV-RM1601BTP-E
-
-
-
Sound pressure level (H/M/L) dB(A)
33-29-25
34-30-26
37-33-30
40-36-33
40-36-33
40-36-33
-
-
-
Dimensions (HxWxD) mm
275 x 700 x 750
275 x 1.000 x 750
275 x 1.400 x 750
275 x 1.400 x 750
275 x 1.400 x 750
275 x 1.400 x 750
-
-
-
Weight kg
23
30
40
40
40
40
-
-
-
External static pressure (stand/upper limit) Pa
30/120
30/120
50/120
50/120
50/120
50/120
-
-
-