FLOOR STANDING RM_FT

Eurovent

Toshiba floor standing unit combines air flow, wide air diffusion and simplified installation to cool and […]

SCOP MAX

4,41

Capacity

5kW – 16kW

Operation

-27°C/+52°C (SDI) -15°C/+46°C (DI)

Warranty

5 years

SCOP MAX

4,41

Capacity

5kW – 16kW

Operation

-27°C/+52°C (SDI) -15°C/+46°C (DI)

Warranty

5 years

Toshiba floor standing unit combines air flow, wide air diffusion and simplified installation to cool and heat large rooms.

Wide Adaptability

Wide Adaptability

  • Broad capacity lineup from 2 to 6HP
  • Connectable in monosplit or twin mode
Comfort

Comfort

  • Wide air flow to cool and heat large areas
  • Horizontal and vertical louvers for optimum air distribution
Easy Installation

Easy Installation

  • Directly positioned on the floor to simplify installation
  • Plug and play product with embedded controller
PERFORMANCE DATA WITH SUPER DIGITAL INVERTER
OUTDOOR UNIT
RAV-GP561ATP-E
RAV-GP801AT-E
RAV-GP1101AT-E
RAV-GP1101AT8-E
RAV-GP1401AT-E
RAV-GP1401AT8-E
RAV-GP1601AT8-E
INDOOR UNIT
RAV-RM561FT-EN
RAV-RM801FT-EN
RAV-RM1101FT-EN
RAV-RM1101FT-EN
RAV-RM1401FT-EN
RAV-RM1401FT-EN
RAV-RM1601FT-EN
Cooling capacity kW
5,0
7,1
10,0
10,0
12,5
12,5
14,0
Cooling range (min. - max.) kW
1,2-5,6
1,9 - 8,0
3,1 - 12,0
2,6 - 12,0
3,1 - 14,0
2,6 - 14,0
2,6 - 16,0
EER
3,51
3,48
4,18
4,07
3,55
3,46
3,19
SEER
5,75
6,24
6,67
5,86
6,1
5,65
5,55
Energy efficiency class C
A+
A++
A++
A+
TBD
TBD
TBD
Seasonal electricity consumption kWh/a C
304
398
524
597
1.229
1.326
1.513
Heating capacity kW
5,6
8,0
11,2
11,2
14,0
14,0
16,0
Heating range (min. - max.) kW
0,9-7,0
1,3 - 11,3
2,6 - 13,0
2,4 - 14,0
2,6 - 16,5
2,4 - 18,0
2,4 - 19,0
COP W/W
3,39
3,38
4,06
4,04
3,53
3,67
3,31
SCOP (Average)
4,20
4,41
4,37
4,00
4,35
4,00
3,96
Energy efficiency class (Average) H
A+
A+
A+
A+
TBD
TBD
TBD
Seasonal electricity consumption kWh/a H
1.266
1.618
2.942
3.774
3.086
4.130
4.238
PERFORMANCE DATA WITH DIGITAL INVERTER
OUTDOOR UNIT
RAV-GM561ATP-E
RAV-GM801ATP-E
RAV-GM1101ATP-E
RAV-GM1101AT8P-E
RAV-GM1401ATP-E
RAV-GM1401AT8P-E
-
INDOOR UNIT
RAV-RM561FT-EN
RAV-RM801FT-EN
RAV-RM1101FT-EN
RAV-RM1101FT-EN
RAV-RM1401FT-EN
RAV-RM1401FT-EN
-
Cooling capacity kW
5,0
6,7
9,5
9,5
12,1
12,1
-
Cooling range (min. - max.) kW
1,5 - 5,6
1,5 - 7,4
3,0 - 11,2
3,0 - 11,2
3,0 - 13,2
3,0 - 13,2
-
EER
2,79
2,11
3,1
3,1
2,57
2,57
-
SEER
5,15
4,89
5,16
5,16
4,86
4,86
-
Energy efficiency class C
A
B
A
A
TBD
TBD
-
Seasonal electricity consumption kWh/a C
340
479
644
644
1.492
1.492
-
Heating capacity kW
5,3
7,7
11,2
11,2
13
13
-
Heating range (min. - max.) kW
1,5 - 6,3
1,5 - 9,0
3,0 - 13,0
3,0 - 13,0
3,0 - 16,0
3,0 - 16,0
-
COP W/W
3,08
2,41
3,51
3,51
3,24
3,24
-
SCOP (Average)
4,00
3,81
3,92
3,92
3,9
3,9
-
Energy efficiency class (Average) H
A+
A
A
A
TBD
TBD
-
Seasonal electricity consumption kWh/a H
980
1.727
2.711
2.711
2.727
2.727
-
PHYSICAL DATA INDOOR
INDOOR UNITS
RAV-RM561FT-EN
RAV-RM801FT-EN
RAV-RM1101FT-EN
RAV-RM1401FT-EN
RAV-RM1601FT-EN
-
-
Sound pressure level (H/M/L) dB(A)
46-42-38
50-45-41
51-46-41
53-48-45
53-48-45
-
-
Dimensions (HxWxD) mm
1.750 x 600 x 210
1.750 x 600 x 210
1.750 x 600 x 390
1.750 x 600 x 390
1.750 x 600 x 390
-
-
Weight kg
44
45
59
59
59
-
-
BROCHURE ( Size: 817.04 KB)